Maintenance and upkeep of fire protection facilities-Electrical fire monitoring system
Release time:
Nov 12,2021
With the development of social and economic development, science and technology continues to progress, the development and application of electric energy is becoming more and more widespread. Electrical equipment in bringing convenience to people at the same time, safety hazards are also increasing. In the usual use of electrical fire monitoring equipment at the same time, to ensure the normal operation of the equipment, strengthen the maintenance and repair of the equipment, so that the equipment can play a more powerful role. Ensure the safety of people's lives and property, and maintain social stability.
Electrical fire monitoring system maintenance procedures
Electrical fire monitor
■ Maintenance methods:
1. no display after the power supply is turned on, check the input power supply, it should work normally, if still no display should be replaced; 2. the display is ambiguous, it should be replaced.
2. display blurring should be replaced monitor; 3.
3. printer failure, first check the print paper installation should be correct, sufficient, manual test print function does not print should be replaced when the printer, can be manually printed but not automatically printed, should be repaired or replaced.
Electrical fire monitoring detector
■ Maintenance methods:
1. electrical fire detector and monitor no communication, cut off the system power restart, check and restore the communication bus connection, open the communication function, check the cause of the failure, repeater failure should be repaired or replaced;.
2. acoustic alarm failure, manually reset the acoustic alarm or release the acoustic alarm shielding, cut off the power to restart, or failure should be repaired or replace the detector; 3.
3. electrical fire monitoring detector automatic power failure should be replaced.
Electrical fire monitoring system maintenance program
Electrical fire monitor
■ Inspection requirements:
1. monthly check the appearance of the electrical fire monitor, sound and light alarm devices, indicators, displays should be normal; 2. monthly check the fault information and alarms, and the alarm should be replaced.
2. monthly check fault information and alarm processing; 3. quarterly check the display of the monitor.
3. Quarterly inspection of the monitor display content.
■ Maintenance methods:
1. Quarterly fastening monitor wiring part; 2.
2. clean the monitor quarterly with a special cleaning tool or soft cloth.
Electrical fire detectors
■ Inspection Requirements:
Monthly check the appearance of the electrical fire monitoring detector, indicator, sound, display should be normal.
■ Maintenance methods:
1. quarterly fastening detector wiring part; 2. quarterly with a special cleaning tool.
2. quarterly with a special cleaning tool or soft cloth cleaning detector.
Electrical fire monitoring system end-of-life conditions
■ Electrical fire monitoring system equipment service life of not more than twelve years, the service life should be scrapped.